Current TransFormer Introduction
CT is divided according to alteration rate of error factor and phase angle from 0.1grade ,0.2grade (standard CT) to 0.5grade,1.ograde,3.0grade (general CT ).
CT is used according to accuracy rate to an electronic watt hour Meter (0.2grade--1.0grade) ,EOCR. EMPR and other current sensor (1.0grade--3.0grade)
 
The limit of standard CT ratio error and phase angle
Ratio Error(%) Phase Angle(Min)
0.025In 0.05In 0.2In 1.0In 1.2In 0.025In 0.05In 0.2In 1.0In 1.2In
0.1급 ±0.20 ±0.16 ±0.12 ±0.10 ±0.10 ±10 ±8 ±6 ±5 ±5
0.2급 ±0.6 ±0.5 ±0.3 ±0.2 ±0.2 ±30 ±25 ±15 ±10 ±10
In shows regular frequency's regular primary current
 
The limit of general meter CT ratio error and phase angle
Ratio Error(%) Phase Angle(Min)
0.05In 0.2In 1.0In 0.05In 0.2In 1.0In
0.5 급 ±1.5 ±0.75 ±0.5 ±90 ±45 ±30
1.0 급 ±3.0 ±1.5 ±1.0 ±180 ±90 ±60
3.0 급 0.5In~1.0In ±3.0 0.5In~1.0In ±180
In shows regular frequency's regular primary current
 